I*v <br /> Email from Raymond von Flue below: <br /> Luis, <br /> 1. Upon reviewing the second draft of the used oil tank assessment for Panella Trucking,more items <br /> were found to be missing or need more clarification: <br /> 1. Remaining service life of tank: What does 50 years with maintenance mean? What type of <br /> maintenance? Does 50 years include the 15 years already used or is it 50 years from the date of the <br /> assessment? The manufacture states that the tank life for this type of use, is 50 years from the date of <br /> manufacture with proper corrosion protection (Painting). If corrosion appears, the area should be <br /> cleaned to bare metal,primed and painted with a suitable coating. <br /> 2. Piping: What type of material? What are the lengths(Fill and Drain)? What are the volumes? <br /> Piping must also be tested. Vacuum line is 1 Y2"schedule 40 about 4'long. Pressure side is 1 %z" <br /> single wire oil resistant rubber hose to top of tank than 1 %z"fill schedule 40 pipe. Volume 389 cubic <br /> inches. 1.7 gals. The drain or unloading line was tested with the tank for a pressure of 5 psi. <br /> 3. Secondary containment: Provide a brief description of materials and coatings used to prevent <br /> migration of wastes from the area Provide a discussion of the compatibility and incompatibility of <br /> the containment surface with any waste it may come in contact with. What does the statement in the <br /> assessment „ all impediments in the concrete block have been sealed with a suitable sealant to <br /> prevent leakage” mean? The containment is by a voids felled reinforced concrete block wall that is <br /> unlined. All concrete is permeable to any liquid but concrete has a very low rate ofpermeability. <br /> Any spills would be discovered long before diesel or used oil could penetrate the 8"concrete block <br /> wall or the concretefloor. All penetrations are caulked with sealant <br /> 4. Clarification of secondary containment calculations:tank volume calculations must include <br /> acillary equipment and piping affiliated with the tank. Please relabel volume calculations as shown in <br /> the model assessment(a) 10%of aggregate volume, (b)volume of largest tank with the boundary,©) <br /> Volume from a 24hr., 25-year storm,(d)calculated volume of area and arrange data as {Larger of(a) <br /> or(b)} + {Containment area x©)) must be<(d)See mathcad sheet attached <br /> 5. Provide a brief description of the site security,Title 22,section 66265.14. <br /> The site is fenced and there is a watchmen on duty 24/7 <br /> If you have any questions,please feel fiee to give me a call. <br /> Raymond von Fliie <br /> Senior Registered Environmental Health Specialist <br /> San Joaquin County <br /> Environmental Health Department <br /> 600 E. Main St. <br /> Stockton CA 95202 <br /> Voice: (209)468-9848 Fax: (209)468-3433 <br /> 4 <br />