Laserfiche WebLink
WALTON_ PRODUCT LINE TESTING <br /> ENGINEERING, INC. DATA SHEET <br /> FFacility: 3B Truck&Auto Plaza 7 Test Equipment Used: AcuRite TN <br /> address: 14749 North Thorton Road Test method By: Manufacturer <br /> city,state Lodi, CA 95241 Line Manufacturer. Smith <br /> Test pate: June 13, 2008 Line mwwai FRP <br /> Line# 1 2 3 4 <br /> Line Product Diesel Sattelite 4 Sattelite 5 Sattelite 6 <br /> Line Diameter [Inches] 3 3 3 3 <br /> Line Length [Feet] (Est) 1000 20 20 20 <br /> Line Capacity [Gallons] (Approx.) 367 7 7 7 <br /> Line Pressure @ Dispenser [PSI] 32 32 32 32 <br /> Test Pressure [PSI](1'h x LP){Min 501 50 50 50 50 <br /> "STP" Isolation Mechanism Ball Valve Ball Vaive Bali Valve Ball Valve <br /> "Disp." Isolation Mechanism Shear Valve Shear Valve Shear Valve Shear Valve <br /> Time Line Shut Down 8:37 AM 8:37 AM 8:37 AM 8:37 AM <br /> Test Start Time 11:15 AM 12:20 PM 12:55 PM 1:30 PM <br /> Test End Time 11:45 AM 1:25 PM 2:00 PM <br /> Test Duration [h:mm] 0:30 0:00 0:30 0 30 <br /> Initial Cylinder Level (ICL) 0.0625 0.0475 0.0725 <br /> Final Cylinder Level (FCL) 0.0650 0.0475 0.0725 <br /> Volume Lost [Gallons] (ICL-FCL) -0.0025 0.0000 0.0000 <br /> Indicated Leak Rate [GPH] -0.0050 0.0000 0.0000 <br /> Pass/ Fail Threshold [GPH] 0.0100 0.0100 0.0100 <br /> TEST RESULT PASS FAIL PASS PASS <br /> Comments: <br /> Could not get Sattelite#4 to pressurize. Filled my Accurlte test cylinder 8 times. Each time the <br /> cylinder would empty In around 10 seconds. <br /> 0 2006 Walton Engineering, Inc. <br />