Laserfiche WebLink
Sprint Corporation Spill Prevention , Control, and Countermeasure Plan <br /> Stockton , CA Switch GENERAL INFORMATION <br /> Table 24 SUMMARY OF OIL STORAGE <br /> Storage <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> South side of parking <br /> 6 ( up to 10 units, Portable Equipment Diesel Fuel 21000 area on south side of 06/2007 <br /> typically) switch building <br /> 7 Oil - Filled Equipment Generator # 1 Lube Oil 61 Adjacent to east side of 09/2015 <br /> switch building <br /> 8 Oil - Filled Equipment Generator #4 Lube Oil 61 Inside north generator 1/1997 <br /> enclosure <br /> 9 Oil - Filled Equipment Elevator Hydraulic 115 Inside switch building Unknown <br /> Oil <br /> 10 Oil - Filled Equipment Elevator Hydraulic 115 Inside switch building Unknown <br /> Oil <br /> 11 Oil - Filled Equipment Transformer Mineral Oil 424 East side of switch 10/2009 <br /> building <br /> 12 Oil - Filled Equipment Transformer Mineral Oil 418 East side of switch 10/2009 <br /> building <br /> 13 Bulk Storage Tank Primary Storage Diesel Fuel 10, 000 East of switch building 1/1994 <br /> ( exempt) ( UST) <br /> Total Aboveground Oil Storage Capacity 16, 594 <br /> Generator #2 and Generator #3 container contain 41 gallons and 27 gallons, respectively, of <br /> lube oil , thus are not subject to 40 CFR 112 . The capacity of the hydraulic vessel reservoirs for <br /> the two elevators were estimated based off of similar elevators at other Sprint facilities . A <br /> second transformer <br /> 4 Sprint Corporation Proprietary and Confidential <br />