The following is an itemized list of underground storage tank violations that have not <br /> been addressed for CHEVRON STATION #307709'` as of January 11, 2018. <br /> Open violations from March 24,2017 inspection <br /> Violation#305-VPH monitoring of the interstitial spaces of the UST system is not maintained. <br /> The S-5 91 vent line and the 91 fill sump vacuum sensor failed when tested. The S-2 87 vent line and 87 fill sump <br /> float liquid sensor failed when tested. The interstitial space of the UST shall be maintained, as designed, under <br /> constant vacuum such that a breach in the primary or secondary containment is detected before the hazardous <br /> substance is released into the environment. The sensors were replaced and retested good during the inspection. <br /> Communication of the vacuum sensors for the vent sump, tank top sumps and under dispenser containments could <br /> not be tested because the bottom ports of the UDCs and the sumps could not be opened to verify communication of <br /> vacuum monitoring throughout the interstitial space of the sumps. Make the ports accessible and notify the EHD of <br /> the test time and date. Notification must be 48 hours prior to the communication testing. <br /> Communication of the vacuum sensors throughout the piping secondary containment was not tested today. <br /> Communication testing of the vacuum sensor zones is required annually. Schedule a test and notify the EHD of the <br /> time and date. Notification must be 48 hours prior to the communication testing. <br /> Page 1 of 1 <br />