Laserfiche WebLink
April 8, 2016 <br />San Joaquin County <br />Environmental Health Department <br />1868 East Hazelton Ave. <br />Stockton, CA 95205 <br />Inspector Fatinah Zareef, <br />Global Marketing <br />T-0 (Terran <br />Our Family of Brands <br />Chevron Corporation <br />145 S. State College <br />Brea, CA 92821 <br />P.O. Box 2292 <br />Brea, CA 92821-2922 <br />JUN 2 3 2016 <br />This letter is in response to the inspection report issued on Mar 31, 2016 to Chevron Station # 307709 located at 10858 Trinity <br />Pkwy. Stockton, CA. <br />Below is our response regarding the 2 items noted in the enclosed inspection report; <br />The S3 All UDCs and S5 91 Vent -Fill sensors failed when tested. <br />o Per the enclosed inspection report, the S3 and S5 sensor float was replaced and retested and passed. <br />Corrected on Site. <br />The diesel VMI line leak detector failed to detect a leak when tested. <br />o Per the enclosed inspection report, the Tanknology service technician replaced the siphon jet valve and <br />purged the line, retested and it passed. Corrected on site. <br />We will consider the above items resolved per this letter. Please contact me directly if you have any questions or concerns. <br />Sincerely, <br />Mohsin Khwaja <br />UST Compliance Coordinator <br />Chevron Stations Inc. <br />145 S. State College., Suite 400 <br />Brea, CA 92821 <br />Office Phone (714) 6713223 <br />Cell Phone (909) 420 5289 <br />Fax (866) 420 0335 <br />(Please use fax cover) <br />Mailto: MohsinKhwaia@Chevron.com <br />Enclosed Documents: Copy of inspection report dated 03/31/2016. <br />