Tanknology <br />Work Order: 2326243 <br />Site Name / ID: CHEVRON 307709 / 307709 <br />Address: 10858 TRINITY PKWY <br />City: STOCKTON <br />LDT 5000 Field Test Apparatus <br />Line Leak Detector Test ENVIRUNMENTAe 1 of 1 <br />L-!!AITN M:PWTa PCWT <br />Date: 3/31/2016 <br />State: CA <br />Zip: 95219 <br />Tank ID <br />T1 <br />T-2 <br />T-3 <br />T-3 <br />Product <br />UNLEADED <br />PREMIUM <br />Diesel <br />Diesel <br />Product Line <br />1 <br />1 <br />1 <br />1 <br />Tested From <br />12 <br />12 <br />12 <br />12 <br />Existing/New <br />Existing <br />Existing <br />Existing <br />Existing <br />Mechanical/Electronic <br />Electronic <br />Electronic <br />Electronic <br />Electronic <br />Manufacturer/Model <br />Veeder Root PLLD <br />Veeder Root PLILD <br />Veeder Root PLILD <br />Veeder Root PLL <br />Serial No. <br />303074 <br />303057 <br />303058 <br />303058 <br />Pump Operating Pressure (psi) <br />28.00 <br />29.00 <br />45.00 <br />45.00 <br />Calibrated Leak (ml/min) <br />189.0 <br />189.0 <br />189.0 <br />189.0 <br />Calibrated Leak (gph) <br />3.00 <br />3.00 <br />3.00 <br />3.00 <br />Holding PSI <br />N/A for Electronic LD's <br />Resiliency (ml) <br />N/A for Electronic Lo's <br />Metering PSI <br />N/A for Electronic Lo's <br />Opening Time (sec) <br />for Electronic LD's <br />Test Results <br />Pass <br />Pass <br />Fail <br />Pass <br />Technician Comments: die I.d. failed initial testing, siphon jet was replaced. product was purged and die I.d. passed. <br />Technician Name: Jarrod Cooke Certification #: 1352 <br />Technician Signature:Expire Date: 2/11/2017 <br />Environmental Compliance for Petroleum Systems <br />© 2016 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com <br />