Laserfiche WebLink
LDT 5000 Field Test Apparatus <br />Tanknology Line Leak Detector Test <br />Work Order: <br />2302101 <br />Site Name / ID: <br />CHEVRON 307709 / 307709 <br />Address: <br />10858 TRINITY PKWY <br />City: <br />STOCKTON <br />Date: 4/27/2012 <br />Page 1 of 1 <br />State: CA Zip: 95219 <br />Tank ID <br />1 <br />2 <br />3 <br />Product <br />UNLEADED <br />PREMIUM <br />Diesel <br />Product Line <br />1 <br />1 <br />1 <br />Tested From <br />12 <br />12 <br />12 <br />Existing/New <br />Existing <br />Existing <br />Existing <br />Mechanical/Electronic <br />Electronic <br />Electronic <br />Electronic <br />Manufacturer/Model <br />Veeder Root PLLD <br />Veeder Root PLLD <br />Veeder Root PLL <br />Serial No. <br />303074 <br />303057 <br />303058 <br />Pump Operating Pressure (psi) <br />28.00 <br />30.00 <br />30.00 <br />Calibrated Leak (mllmin) <br />189.0 <br />189.0 <br />189.0 <br />Calibrated Leak (gph) <br />3.00 <br />3.00 <br />3.00 <br />Holding PSI <br />'NIA for Electronic Lo's <br />Resiliency (ml) <br />"NIA for Electronic Lo's <br />1500.00 <br />Metering PSI <br />'NIA for Electronic Lo's <br />Opening Time (sec) <br />*N/A for Electronic Lo's <br />Test Results <br />Pass <br />Pass <br />Fail <br />Technician Comments:. die I.d. is inconclusive due to high resiliency.syphon jet valve was replaced and 100 gal was <br />pumped with no change in resiliency. <br />Technician Name <br />Technician Signature: <br />Jarrod Cooke Certification #: 1352 <br />Environmental Compliance for Petroleum Systems <br />02010Tankndogy Inc, Ausin,TX All rights reserved tankndogy.com <br />