Laserfiche WebLink
Chevron <br />May 9, 2011 <br />San Joaquin County Environmental Health Department <br />600 East Main Street <br />Stockton, California 95202-3029 <br />Global Marketing <br />Our fa,,IV of Waols <br />Chevron Corporation <br />145 S. State College <br />Brea, CA 92821 <br />P.O. Box 2292 <br />Brea, CA 92821-2922 <br />RECEIVED <br />MAY 12 2011 <br />Inspector Garrett Backus, ENVIRONMENTAL HEALTH <br />PERMIT/SERVICES <br />This letter is in response to the UST inspection report issued on April 29, 2011 to Chevron Station #307709, located <br />at 10858 Trinity Parkway Stockton, CA 95219. <br />Below is our response regarding the 1 item noted in the attached inspection report. <br />■ 17. The diesel line leak detector failed to detect a leak when tested. All line leak detectors shall be capable <br />of detecting a 3 gallon per hour leak at 10 psi. The service technician changed the siphon jet, retested it, <br />and it passed. <br />• Enclosed are the passing LLD test results for diesel. As noted by you in your inspection <br />report "The service technician changed the siphon jet, retested it, and it passed". <br />Please contact me directly if you have any questions or concerns. <br />Sincerely, � A <br />F.C�1C-Ftc`� � l�Cl��t2Z� <br />Andrea Vilchis <br />UST Compliance Coordinator <br />Chevron Stations Inc. <br />145 S. State College., Suite 400 <br />Brea, CA 92821 <br />Office Phone (714) 671-3223 <br />Mailto: AVilchis(cbChevron.com <br />Enclosed Documents: Copy of the UST inspection report dated 4/29/2011; Passing LLD test results for <br />diesel; Return to Compliance Certification <br />