Laserfiche WebLink
Page 1 of 1 <br />Daniel A. Erickson <br />From: Garry DiMaggio [garryd@dimaggiomaintenance.com] <br />Sent: Monday, November 17, 2008 9:45 AM <br />To: Daniel A. Erickson <br />Cc: Richard DiMaggio; Rodney Dimaggio <br />Subject: Detail Sump Repair with 7789.pdf attachment with noted correction <br />Attachments: 7789. PDF <br />Exsplation for Item #32 page 5 L16, L18, L20, L26 Inspect, Repair and test new levels. <br />L16 L18 L26 had NO Alarms or Visual Brine leak on day of 07-29-08 on these three <br />sensors Brine was added and used a visual test by putting new levels and marking brine tube with <br />tape and putting the time and date when new levels were added. <br />L26 had Alarm and visual brine in bottom of UDC Sump . Inspected and found broken hose clamp <br />with brine leakage at this point. Also found a paste like material Blockage in UDC brine Vent. This <br />would cause brine not to level out correct in UDC. So we cleard Blockage and was able to add <br />new Brine levels with ease. Performed same visual test and marked new levels with tape and <br />putting the time and date when new levels were added. Brine tubes had over 8 hours of testing <br />on L16 L18 L20 L26. No Visual leaks or Visual loss of Brine was noted. <br />Thank you, <br />Garry DiMaggio <br />661-325-7060 Office <br />661-609-1753 Cell <br />garryd-di.maggiomaintenance.com <br />11/17/2008 <br />