Laserfiche WebLink
Phil-Tite Installation and MaliiLenance Manual, Page 21 <br />Figure D-1 <br />Phil-Tite Model M/F4X4 Riser Adaptor <br />PHIL-TITE M/F4X4 RISER ADAPTOR <br />The Phil-Tite M/F4X4 RiserAdaptor is designed to provide a flat, true sealing surface for the <br />installation of a gasket sealed, threaded component such as a Spill Container, Threaded <br />Adaptor or storage tank gauging device. <br />INSTALLATION: <br />1. If installing a Spill Container on the M/F4X4, determine the final riser height required to meet <br />finished grade and then subtract 1-3/4" to include the M/F4X4 RiserAdaptor. For all other <br />components, determine the desired final riser height including the M/F4X4 Cut and thread the <br />riser pipe to the appropriate height. <br />2. Apply a gasoline resistant. non -hardening thread sealant to the threads of the riser pipe only. <br />By hand, thread the M/F4X4 onto the riser pipe <br />3. Using an approved Installation Tool (Phil-Tite T-7043-1 Tool Kit), tighten the M/F4X4 onto the <br />riser to a torque value between 150 and 175 Foot -Pounds. <br />4. If installing a drop tube at the product fill riser, install the provided drop tube gasket under the <br />drop tube flange and insert the tube into the tank. <br />5. Install a Spill Container, threaded adaptor or tank gauging equipment onto the RiserAdaptor <br />ensuring that it is installed in conjunction with the Manufacturers Recommended Installa- <br />tion Instructions. <br />WARNING! THE USE OF UNAPPROVED TOOLS OR IMPROPER INSTALLATION WILL <br />VOID ANY AND ALL APPLIED WARRANTIES. <br />June 2005 <br />