Laserfiche WebLink
INDIVIDUAL TANK INFORMATION AND TEST RESULTS <br />P, Tanknology <br />8501 N MOPAC EXPRESSWAY, SUITE 400 <br />TEST DATE: 12/28/07 <br />AUSTIN, TEXAS 78759 (512) 451-6334 WORK ORDER NUMBER: 2253662 <br />CLIENT: JMM MANAGEMENT GROUP, <br />SITE: QUICK STUFF #7789 <br />Tank ID: 3 <br />Tank manifolded: No Bottom to top fill in inches: 118.0 <br />Product: DIESEL <br />Vent manifolded: NO Bottom to grade in inches: <br />Capacity in gallons: 7,817 Vapor <br />recovery manifolded: NO Fill pipe length in inches: <br />Diameter in inches: 118.00 <br />Overfill protection: YES Fill pipe diameter in inches: <br />Length in inches: 167 <br />Overspill protection: YES Stage I vapor recovery: NONE <br />Material: DW FIBERG <br />Installed: ATG Stage II vapor recovery: NONE <br />CP installed on: <br />COMMENTS <br />TANK TEST RESULTS Test Method: NONE <br />LEAK DETECTOR TEST RESULTS Test method: <br />PSI at tank bottom: <br />New/passed Failed/replaced New/passed Failed/replaced <br />Fluid level in inches: <br />L.D. #1 L.D. #1 L.D. #2 L.D. #2 <br />UFT/OFT: <br />Make: <br />Fluid volume in gallons: <br />Model: <br />Tank water level in inches: <br />S/N: <br />Test time: NOT <br />Open time in sec: <br />Number of thermisters: TESTED <br />Holding psi: NOT NOT <br />Specific gravity: <br />Resiliency cc: TESTED TESTED <br />Water table depth in inches: <br />Test leak rate ml/m: <br />Determined by (method): <br />Metering psi: <br />Leak rate in gph: <br />Calib. leak in gph: <br />Result: <br />Results: <br />COMMENTS <br />COMMENTS <br />ULLAGE TEST RESULTS Test Method: NONE <br />LINE TEST RESULTS Test type: TLD -1 <br />Test time: <br />Ullage volume: <br />Material: DW FIBERG <br />Ullage pressure: <br />Diameter (in): 2.0 <br />Results: <br />Length (ft): 150.0 <br />Test psi: 50 <br />DATA FOR UTS-4T ONLY: <br />Bleedback cc: 0 <br />Time of test 1: <br />Test time (min): 0 <br />Temperature: NOT <br />Start time: 09:42 NOT NOT NOT <br />Flow rate (cfh): TESTED <br />End time: TESTED TESTED TESTED <br />Time of test 2: <br />Final gph: 0.049 <br />Temperature: <br />Result: FAIL <br />Flow rate (cfh): <br />Pump type: PRESSURE <br />Time of test 3: <br />Pump make: FE PETRO <br />Temperature: <br />Flow rate (cfh): <br />Impact Valves Operational: NO <br />COMMENTS <br />COMMENTS <br />Found, line leaking thru disp #4 dsl shear valve. <br />Printed 01/14/2008 08:31 ACRAMER <br />