Laserfiche WebLink
I MARK OF SERVICE <br />May 1, 1986 <br />E -Z Serve of California <br />P. 0. Box 3550 <br />Ontario, California 91761 <br />Attention: Mike Buckmaster <br />Re: Madsen Sunrise Dairy <br />239 South Stockton, Ripon, California <br />Dear Mike: <br />0 <br />FEB 26 1,38- <br />ENVIROMENTAL HEALTH <br />FERMIT/SERVICES <br />On April 28, 1986, a Petro Tite System Test was performed at the <br />above -referenced location. The test was performed by Larry Carver, <br />FHEMCO Technician. The NFPA Code 329.02 criteria for a tight <br />system is a maximum loss of .05 gallons per hour. Because of the <br />almost infinite variables involved, this is not intended to be a <br />mathematical tolerance and is not the permission of actual leakage. <br />SYSTEM TEST: <br />No. 1 - North <br />Size - 6,000 Gallons <br />Product - Regular <br />The test showed a plus .018 gallons per hour. <br />Based on the above criteria, we find the tank tested <br />mathematically tight. <br />No. 2 - Middle <br />Size - 8, 000 Gallons <br />Product - Regular <br />The test showed a plus .018 gallons per hour. <br />Based on the above criteria, we find the tank tested <br />mathematically tight. <br />F & H Equipment Maintenance Co. <br />1100 North "J" Street <br />Post Office Box 88 — Tulare, California 93275-0088 Phone (209) 688-2977 <br />