Laserfiche WebLink
Item 718 (720) - Failed to provide sufficient secondary containment capacity for mobile or portable <br /> containers <br /> ® EPA updated the SPCC rule in 2006 and removed the requirement for sized secondary containment <br /> for mobile refuelers (" dike or catchment basin , of sufficient size to contain the capacity of the largest <br /> compartment or container on a mobile refueler along with enough room to contain <br /> precipitation ") . The requirement for general secondary containment remains in place . The general <br /> secondary containment requirements do not require a specific size or quantity for secondary <br /> containment ; they do require appropriate systems to prevent spilled oil from escaping . Active <br /> systems can be used , such as spill mats , storm drain covers , and dams used to block or prevent the <br /> flow of oil . A spill kit is provided on the mobile refueler to deploy if a spill occurs . <br /> Item 723 (726) - Failed to regularly inspect aboveground valves , piping , and appurtenances <br /> • The aboveground valves , piping , and appurtenances will be inspected and documented on a regular <br /> basis . <br /> If you have any questions regarding this plan please contact Thelma Sass , Risk Control Manager II at (209 ) <br /> 931 -7416 <br /> Regards , <br /> �A <br /> Glenn King <br /> General Manager <br /> Supervalu , Inc . — Stockton Distribution Center <br /> Inc . : Return to Compliance Certification <br /> SPCC Plan <br /> 3 <br />