Laserfiche WebLink
INDIVIDUAL TANK INFORMATION AND TEST RESULTS <br />P, 7anid7oloyy <br />TEST DATE: 09/27/06 <br />8501 N MOPAC EXPRESSWAY, SUITE 400 WORK ORDER NUMBER2244819 <br />CLIENT:TITAN MANAGEMENT <br />AUSTIN, TEXAS 78759 (512) 451-6334 SITE:TOYS "R" US <br />TANK INFORMATION " <br />Tank ID: 1 <br />Tank manifolded: NO Bottom to top fill in inches: <br />113.0 <br />Product: DIESEL <br />Vent manifolded: NO Bottom to grade in inches: <br />119.0 <br />Capacity in gallons: 10,309 <br />Vapor recovery manifolded: No Fill pipe length in inches: <br />17.0 <br />Diameter in inches: 96.00 <br />Overfill protection: YES Fill pipe diameter in inches: <br />4.0 <br />Length in inches: 340 <br />Overspill protection: YES Stage I vapor recovery: <br />NONE <br />Material: DW STEEL <br />Installed: ATG Stage II vapor recovery: <br />NONE <br />CP installed on: <br />COMMENTS <br />TANK TEST RESULTS Test Method:VacuTect <br />LEAK DETECTOR TEST RESULTS Test method: FTA <br />Start (in) <br />End (in) <br />Dipped Water Level: 0.00 <br />0.00 <br />New/passed Failed/replaced New/passed Failed/replaced <br />Dipped Product Level: 37.00 <br />37.00 <br />L.D. #1 L.D. #1 L.D. #2 <br />L.D. #2 <br />Probe Water Level: 0.087 <br />0.087 <br />Make: <br />Ingress Detected: Water N Bubble <br />N UllageN <br />Model: <br />S/N: <br />Test time: 08:49-10:14 <br />Open time in sec: <br />Inclinometer reading: <br />0.00 <br />Holding psi: <br />VacuTect Test Type: single <br />tank <br />Resiliency c s NOT xoT <br />VacuTect Probe Entry Point: Gauge <br />Test leak rate ml/m: TESTED TESTED <br />Pressure Set Point: <br />-0.50 <br />Metering psi: <br />Tank water level in inches: <br />0.00 <br />Calib. leak in gph: <br />Water table depth in inches: <br />119.00 <br />Results: <br />Determined by (method): <br />Result: <br />PASS <br />COMMENTS <br />COMMENTS <br />LINE TEST RESULTS Test type: TLD -1 <br />LINE <br />A B C D <br />Material: DW FIBERG <br />Diameter (in): <br />2.0 <br />Length (ft): <br />16.0 <br />Test psi: <br />-1 <br />Bleedback cc: <br />0 <br />Test time (min): <br />85 NOT NOT NOT <br />Start time: <br />08: 49 TESTED TESTED TESTED <br />End time: <br />10:14 <br />Final gph: <br />0.000 <br />Result: <br />PASS <br />Pump type: <br />SUCTION <br />Pump make: <br />UNKNOWN <br />COMMENTS <br />Impact Valves Operational: UNKNOWN <br />TESTED LINE WITH TANK. REMOVED <br />FOOT VALVE. <br />Printed 10/03/2006 08:47 <br />