Laserfiche WebLink
INDIVIDUAL TANK INFORMATION AND TEST RESULTS <br />Ji Tanknology <br />TEST DATE: 09/14/05 <br />8501 N MOPAC EXPRESSWAY, SUITE 400 WORK ORDER NUMBER2238521 <br />CLIENT: TITAN MANAGEMENT <br />AUSTIN, TEXAS 78759 (512) 451-6334 SITE: TOYS "R" US <br />Tank ID: 1 <br />Tank manifolded: NO Bottom to top fill in inches: <br />107.0 <br />Product: DIESEL <br />Vent manifolded: NO Bottom to grade in inches: <br />119.0 <br />Capacity in gallons: 10,309 <br />Vapor recovery manifolded: No Fill pipe length in inches: <br />12.0 <br />Diameter in inches: 95.00 <br />Overfill protection: YES Fill pipe diameter in inches: <br />4.0 <br />Length in inches: 340 <br />Overspill protection: YES Stage I vapor recovery: <br />NONE <br />Material: DW STEEL <br />Installed: ATG Stage II vapor recovery: <br />NONE <br />CP installed on: <br />COMMENTS <br />TANK TEST RESULTS Test Method: VacuTect <br />LEAK DETECTOR TEST RESULTS Test method: FTA <br />Start (in) <br />End (in) <br />Dipped Water Level: 1.00 <br />1.00 <br />New/passed Failed/replaced New/passed Failed/replaced <br />Dipped Product Level: 34.50 <br />34.50 <br />L.D. #1 L.D. #1 L.D. #2 <br />L.D. #2 <br />Probe Water Level: 1.099 <br />1.099 <br />Make: <br />Ingress Detected: Water N Bubble <br />N UllageN <br />Model: <br />S/N: <br />Test time: 11:14-12:28 <br />Open time in sec: <br />Inclinometer reading: <br />0.00 <br />Holding psi: <br />VacuTect Test Type: Single <br />tank <br />Resiliency cc: NOT NOT <br />VacuTect Probe Entry Point: Gauge <br />Test leak rate ml/m: TESTED TESTED <br />Pressure Set Point: <br />-0.50 <br />Metering psi: <br />Tank water level in inches: <br />1.00 <br />Calib. leak in gph: <br />Water table depth in inches: <br />60.00 <br />Results: <br />Determined by (method): <br />NO WELL <br />Result: <br />PASS <br />COMMENTS <br />COMMENTS <br />PASSED. <br />i <br />LINE TEST RESULTS Test type: TLD-1 <br />LINE <br />A B C D <br />Material: DW FIBERG <br />Diameter (in): <br />2.0 <br />Length (ft): <br />16.0 <br />Test psi: <br />1 <br />Bleedback cc: <br />0 <br />Test time (min): <br />74 NOT NOT NOT <br />Start time: <br />11:14 TESTED TESTED TESTED <br />End time: <br />12:28 <br />Final gph: <br />0.000 <br />Result: <br />PASS <br />Pump type: <br />SUCTION <br />Pump make: <br />UNKNOWN <br />COMMENTS <br />Impact Valves Operational: UNKNOWN <br />Printed 09/15/2005 17:21 <br />