Laserfiche WebLink
(Q0 TAff-TEK <br />TANK TEK ENVIRONMENTAL CORPORATION E I V E!'D <br />MAR 2 5 2016 <br />PRESSURIZED PIPING LEAK DETECTION CERTIFICATION,SHEET <br />Date: 311112016 Work Order # 16031102-7 <br />Location: VALLEY PACIFIC Country Market Contact: MIKE ELIASON <br />1524 FRESNO AVENUE <br />STOCKTON CA 95206 Telephone: (209) 948-9412 <br />SUMP # <br />112 <br />314 <br />PRODUCT <br />DIESEL <br />DIESEL <br />LD TYPE M echanlcal, PLLD, (P)LLD <br />M <br />M <br />LD MANUFACTURER <br />VMI <br />VMI <br />LD MODEL <br />LD2000 <br />LD2000 <br />LD SERIAL NUMBER <br />07011359 <br />00011316 <br />SUMP CONDITION <br />DRY <br />DRY <br />RESILIENCY <br />150 ML <br />150 ML <br />OPERATING PRESSURE <br />30 PSI <br />26 PSI <br />OPENING TIME <br />4 SEC <br />6 SEC <br />METERING PRESSURE <br />10 PSI <br />10 PSI <br />FUNCTIONAL ELEMENT HOLDING PRESSURE <br />22 PSI <br />22 PSI <br />LEAK RATE LD DETECTED <br />3 GPH <br />3 GPH <br />DOES LD DETECT 3 GPH LEAK RATE? <br />YES <br />YES <br />DOES VEEDER-ROOT CONSOLE ALARM? <br />NIA <br />NIA <br />LD PASS OR FAIL? <br />PASS <br />PASS <br />Comments: <br />Technician: RICHARD THOMAS Contractor Lic. # 803705 <br />Signature: <br />PO BOX 5850, RIVERSIDE, CA 92517-5850 TEL 951-779-4999 FAX 951-788-7089 <br />W W W.TAN K-TEK.COM <br />