Laserfiche WebLink
TANdf-TEIf CC <br />TANK-TEK ENVIRONMENTAL CORPOHATIOARECLI <br />EC <br />APR 0 6 2015 <br />ENVIRONMENTAL <br />:L4 F: Q I TU r1C0A 0 r4 RCR M <br />PRESSURIZED PIPING LEAK DETECTION CERTIFICATION SHEET <br />Date: 311212n,5 <br />Location: COUNTRY MARKET <br />1524 FRESNO AVENUE <br />STOCKTON CA 95206 <br />Work Order # 15n312n2-7 <br />Contact: M/KF FI ldAnAI <br />Telephone: (209) 948-9412 <br />SUMP # <br />3/4 <br />1/2 <br />PRODUCT <br />DIESEL <br />DIESEL <br />LD TYPE Mechanical, (W)PLLD, (P)LLD I <br />M <br />LD MANUFACTURER <br />VMI <br />VMI <br />LD MODEL <br />LD2000 <br />LD2000 <br />LD SERIAL NUMBER <br />See Comments <br />See Comments <br />SUMP CONDITION <br />DRY <br />DRY <br />RESILIENCY <br />150 ML <br />200 ML <br />OPERATING PRESSURE <br />28 PSI <br />28 PS8 <br />OPENING TIME <br />4 SEC <br />4 SEC <br />METERING PRESSURE <br />10 PSI <br />10 PSI <br />FUNCTIONAL ELEMENT HOLDING PRESSURE <br />12 PSI <br />12 PSI <br />LEAK RATE LD DETECTED <br />3 GPH <br />3 GPH <br />DOES LD DETECT 3 GPH LEAK RATE? <br />YES <br />YES <br />DOES VEEDER-ROOT CONSOLE ALARM? <br />N/A <br />N/A <br />LD PASS OR FAIL? <br />PASS <br />PASS <br />Comments: <br />LEAK DETECTOR SERIAL NUMBERS WERE LOST WITH ORIGINAL PAPER <br />SEE ATTACHED POLICE REPORT. <br />Technician: RICHARn THOMdS <br />Signature: <br />WHICH WAS STOLEN. <br />Contractor Lic. # 803705 <br />PO BOX 5850, RIVERSIDE, CA 92517-5850 TEL 951-779-4999 FAX 951-788-7089 <br />W WW.TANK-TEK.COM <br />