Laserfiche WebLink
n <br />PRESSURIZED PIPING LEAK DETECTION CERTIFICATION SHEET <br />Date: JUN 19. 2008 <br />Location: COUNTRYMARKFT <br />1524 FRESNO AVENUE <br />STOCKTON, CA 95206 <br />Work Order # 08061901-2 <br />Contact: MIKE ELIASON <br />Telephone: (209) 948-9412 <br />SUMP # <br />1 <br />1 <br />PRODUCT <br />DIESEL <br />DIESEL <br />LD TYPE Mechanical, W PLLD, (P)LLD I <br />M <br />M <br />LD MANUFACTURER <br />VAPORLESS <br />VAPORLESS <br />LD MODEL <br />LD 2000 <br />LD 2000 <br />LD SERIAL NUMBER <br />07011359 <br />01011360 <br />SUMP CONDITION <br />DRY <br />DRY <br />RESILIENCY <br />140 ML <br />75 ML <br />OPERATING PRESSURE <br />30 PSI <br />28 PSI <br />OPENING TIME <br />.0203 SEC <br />.0302 SEC <br />METERING PRESSURE <br />10 PSI <br />10 PSI <br />FUNCTIONAL ELEMENT HOLDING PRESSURE <br />20 PSI <br />18 PSI <br />LEAK RATE LD DETECTED <br />3 GPH <br />3 GPH <br />DOES LD DETECT 3 GPH LEAK RATE? <br />YES <br />YES <br />DOES VEEDER-ROOT CONSOLE ALARM? <br />N/A <br />N/A <br />LD PASS OR FAIL? <br />PASS <br />PASS <br />Comments: <br />Technician: Robert Neimeyer Contractor Lic. # 803705 <br />Signature:` <br />TANK-TEK ENVIRONMENTAL CORPORATION <br />607 Elmira Road, PMB 336, Vacaville, CA 95687 — Ph. (707) 446-6151 - Fax (707) 446-6192 - E-mail: tank-tek@cwnet.com <br />31828 Cercle Chambertin, Temecula, CA 92591 — Ph. (951) 699-8058 - Fax (951) 699-8059 - E-mail: drbtanktek@sdccu.net <br />