Laserfiche WebLink
Inspection Summary <br />An STI SP001 formal external inspection that included visual examination was conducted. The inspection was completed on <br />12/5/2017. The tank is located at Tracy Municipal Airport, 5749 Tracy Blvd. in Tracy, CA. The following is a detailed report of the <br />inspection including findinas and recommendations. <br />1.0 GenerallTank Information <br />General Information <br />Facility Name <br />•.Comments/Recommendations <br />Tracy Municipal Airport <br />Facility ID <br />AIRPORT <br />Compliance Records Available? <br />N/A <br />anknology Work Order No. <br />6702244 <br />Other <br />N/A <br />Tank 6ata <br />Tank Nameplate <br />Observations <br />Underwriters Laboratories Inc. <br />Comments/Recommendations <br />Tank Name / Number <br />3 <br />Tank Layout (Horizontal, Vertical, other) <br />Horizontal <br />Tank Design (Single wall, double wall, other) Double Wall <br />Tank Construction Material (carbon, <br />stainless, other) <br />Carbon Steel <br />Tank size (nominal gallons) <br />15882 <br />Tank Shape <br />Cylinder <br />Tank Length <br />408inches <br />Tank width / diameter / circumference <br />107 inches <br />Tank Height <br />118 inches <br />Tank Contents <br />AVGAS100 <br />Cathodic Protection <br />None <br />Continuous Release Detection Method <br />(CRDM) <br />Elevated /Visual <br />Release Prevention Barrier (RPB) <br />IDouble Wall <br />Spill Control <br />lConcrete Pad <br />Other <br />SupportsFoundations And <br />Tank Foundation Type <br />N/A <br />•.Comments/Recommendations <br />Concrete Pad <br />Tank Foundation Condition <br />Good <br />Tank Support Type <br />Steel Legs <br />Tank Support Condition <br />Fair <br />Tank supports have paint failure and corrosion, <br />recommend cleaning and painting to prevent further <br />ama e. <br />ank Protection (bollards, fence, other) <br />Fence <br />Fence is in good condition. <br />Other <br />Signage•.Comments/Recommendations <br />Filling Procedures Posted At Fill As <br />Required? <br />N/A <br />Yes <br />"No Smoking" Signage Present As Required?Yes <br />Emergency Contact Numbers Posted As <br />Required? <br />No <br />Emergency plan is required and should include posting <br />of emergency contact numbers. <br />Tank Capacity And Tank ID Posted On The <br />Tank As Required? <br />Yes <br />NFPA Signage - On The Tank, At Facility <br />Entrance, And As Designated By Fire Code <br />Official. Labels Include Contents And NFPA <br />704 Diamond Hazard Signs. <br />Yes <br />Other <br />N/A <br />