Laserfiche WebLink
R EIVED <br /> API 653Tank Inspection 201 <br /> NCPA CTI,Lodi,CA FEB 2��6 <br /> ENVIRONMIENTAL <br /> HEAL rH DFF4ZTMFNtT <br /> Tank Inspection Report Form <br /> Inspection Standard: API 653 External, with ultrasonic thickness measurement of the shell and <br /> internal inspection pictures from the roof hatch. <br /> Tank Owner: NCPA <br /> Tank Location: 2131 West Turner Rd., Lodi, CA 95240 <br /> Tank Name: Source 1, Diesel Fuel Storage Tank <br /> API STANDARD 650 <br /> APPENDIX YEAR COMPLETED <br /> EDITION REVISION NUMBER �] <br /> NOMINAL DIAMETERS NOMINAL HEIGHT <br /> NOMINAL CAPACITY - DESIGN LIQUID LEVEL <br /> DESIGN SPECIFIC GRAVITY MAXIMUM OPERATING TEMP. <br /> DESIGN PRESSURE PARTIAL STRESS RELIEF <br /> MANUFACTURER'S SERIAL NO. PURCHASER'S TANK NO. 0 <br /> FABRICATED BY PITTSBURGH DES MOINES CORP. <br /> ERECTED BY PITTSBURGH DES MOINES CORP. <br /> SHELL COURSE MATERIAL <br /> Figure 1 <br /> Tank Name Plate <br /> API 650 minimums for this size tank are 0.25" bottom and 0.19" minimum shell <br /> Date of Inspection: 1/21/16 <br /> Discrepancies: <br /> 1. Vegetation and dirt must be removed from the exterior bottom of the tank. <br /> 2. Tank anchors and appurtenances require painting. <br /> 3. Tank gauge indicator requires painting. <br /> 4. Tank gauge calibration must be checked annually. <br /> John Strandberg PE,rwaterguyCdrwaterguy.com 1-866-388-0404 11 P a g e <br />