JONES COVEY GROVP, INC. <br /> P E VE LO P E RS/CONSTRUCTORS <br /> MECHANICAL / ELECTRONIC LEAK DETECTOR CERTIFICATION <br /> 5/15/2014 <br /> SITE: Pilot Flying J 617 DATE: <br /> State Facility# CONTACT: Manager <br /> PHONE: <br /> JOB#: WO 26630 <br /> Tank # T1 T2 <br /> Product Diesel Diesel <br /> FIN <br /> LD Manufacturer VMI VMI R Ec"' FE IV EJ�s' <br /> LD Model LD3000 LD3000 JUN_O 2 2014 <br /> Sump Condition Clean/Dry Clean/Dry ENVIIIONMFNTAL HEALTH <br /> npp""R:fMEN'� <br /> Operation Pressure <br /> (PSI) <br /> 42 40 <br /> Opening Time (Sec) 5 6 <br /> Metering Pressure <br /> (PSI) <br /> 25 22 <br /> Functional Element <br /> 36 37 <br /> Holding Pressure <br /> Leak Rate LD Detected 3 3 <br /> (GPH) <br /> Does LD Detect 3 GPH Yes Yes <br /> Leak Rate? <br /> LD Serial 00309016 00309015 <br /> Comments: <br /> Technician Issac Garcia License Number 804431 <br /> Signature <br /> 9595 Lucas Ranch Rd. # 100 Rancho Cucamonga, CA 91730 <br /> Office (909)972-7581 Fax (909) 484-0300 Fax California State License#804431 A,B,HAZ <br />