Laserfiche WebLink
Central Petroleum Maintenal;e %or (925) 462-4060 <br /> 176 Wyoming Street, P.O. Box 211 FAX (925) 462-8352 <br /> Pleasanton, CA 94566 <br /> VAPORLESS MANUFACTURING, INC. <br /> LDT-890 Leak Detector Test Record <br /> Customer Date <br /> Address City <br /> 3\1 QQ <br /> Technician Product <br /> Submersible Pump Identification <br /> Manufacturer Model No. Serial Number <br /> Leak Detector Identification <br /> Manufacturer �,a �p r�r�l Description Other Style Leak Detector <br /> Diaphram-Type <br /> Piston Type / <br /> Tamper-proof seal installed? Yes No V <br /> Leak Detector in Submersible Pump <br /> Test At Dispenser <br /> Retest <br /> 1. Operating Pump Pressure 3 psi (para.15) 1. psi (para.15) <br /> 2. Gallons per hour rate _3( 0 (para.22) 2. (para. 22) <br /> 3. Line Pressure with pump shut off_.2Q psi (para.25) 3. psi <br /> 4. Bleedback Test with pump off a ml (para.26) 4. ml (para.26) <br /> 5. Step-through time to full flow-3seconds (para.30) 5. seconds (para.30) <br /> 6. Leak detector stays in leak search position (para. 42) Yes: 6. Yes:_ <br /> No: / No: <br /> 7. Leak Detector Test: Pass:V 7. Pass:_ <br /> Fail: Fail: <br /> Note: Pass=Leak Detector fits test protocal <br /> Failed=Leak Detector fails test protocal <br /> 8. Leak Detector Replaced Yes 8. Yes:_ <br /> No:— No: <br /> SUB - PUMP APPROXIMATE OPERATING PRESSURE <br /> Red Jacket 3/4 HP 28 PSI <br /> Red Jacket 1 1/2 HP 30 PSI <br /> Red Jacket X3 1 1/2 HP 43 PSI <br /> FE Petro 1 1/2 HP 30 PSI <br />