LDT 5000 Field Test Apparatus MAR 0 Gage 1 bf 1 <br /> Tanknology Line Leak Detector Test ENVIR NA'1nw,, `i p <br /> Work Order: 2322332 Date: 2/27/2015 <br /> Site Name/ID: TRACY PETRO/Tracy Petro <br /> Address: 3400 N. MACARTHUR DR <br /> City: TRACY State: CA Zip: 95376 <br /> rank ID T1 T2 T3 <br /> rotluct PREMIUM REGULAR Diesel <br /> rotluct Line 1 1 1 <br /> Tested From 8 8 8 <br /> xisting/New Existing Existing Existing <br /> echanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-200C Vaporless LD-200C Vaporless LD-200 <br /> Serial No. 10051164 06101129 03120005 <br /> ump Operating Pressure(psi) 35.00 38.00 33.00 <br /> alibrated Leak(ml/min) 189.0 189.0 189.0 <br /> alibratetl Leak(gPh) 3.00 3.00 3.00 <br /> lotting PSI 35.00 38.00 33.00 <br /> NIA for Electronic LO's <br /> esiliency(ml) 250.00 310.00 180.00 <br /> NIA for Electronic Lo's <br /> etering PSI 24 25 20 <br /> NIA for Electronic Lo's <br /> peeing Time(sec) 3 3 2 <br /> NIA for Electronic Lo's <br /> est Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Jarrod Cooke Certification#: 1352 <br /> Technician Signature: <br /> Expire Date: 2/10/2015 <br /> Environmental Compliance for Petroleum Systems <br /> 02015TanknclWyle,.Ausn.Tx. All,phlsrese W WnWdo,,. m <br />