Laserfiche WebLink
..R k <br /> The following is an itemized list of hazardous waste violations that have not been addressed <br /> for J & L Market as of June 09, 2015. <br /> Open violations from May 23, 2013 inspection <br /> Violation #101 - Failed to prepare a written SPCC Plan in accordance with CFR Part 112 <br /> Facility has an APSA regulated shell capacity of 10,000 gallons. No Spill Prevention & Countermeasure Control <br /> (SPCC) Plan was available on site. All facilities which have an APSA regulated shell capacity of 1,320 gallons or <br /> greater shall prepare a written SPCC Plan which meets all of the requirements of the Code of Federal <br /> Regulations Title 40, Part 112. This facility qualifies as a Tier II facility which has no aboveground oil storage <br /> containers with a capacity greater than 10,000 gallons. Immediately prepare a SPCC Plan in accordance with 40 <br /> CFR Part 112, which will include all aboveground petroleum storage containers 55 gallons or larger. A template <br /> for Tier II SPCC Plans can be found on the EHD website under the program Aboveground Petroleum Storage Act. <br /> Submit a copy of the properly Professional Engineer(PE) or self-certified SPCC Plan to the EHD for review by <br /> June 23. (This copy will be returned to the facility after review.) A copy shall be maintained on site at all times. <br /> Page 1 of 1 <br />