Laserfiche WebLink
TANKNOLOGY - UNDERGROUND LEAK DETECTION SYSTEM - (V3.12) Page 1 <br />SERVICE STATION HN9NblHNU5b9N4642 - Jun 2% IH3, 21: <br />lr.:!b — F --r �E3- I ... Ei 0,11111-0 dC,� 'y <br />TEST DATE <br />: Jun 29, 1993 <br />START TIME <br />: 21:33:00 <br />CLIENT <br />: CHEVRON USA <br />LOCATION NAME <br />: SERVICE STATION <br />LOCATION CODE <br />: 95775 <br />* TANK CONFIGURATION <br />: Tandem <br />TANK CONTENTS <br />: PLUS/SUN <br />TANK NUMBER <br />: 02 <br />03 <br />TANK DIAMETER <br />: 91 <br />91 in <br />TANK CAPACITY <br />: 10000 <br />10000 G <br />TANK MANUFACTURER <br />: <br />TANK MATERIAL <br />: Fibreglass <br />Fibreglass <br />TANK REGISTRATION # <br />: <br />TANK DATE INSTALLED <br />INITIAL DIPPED FUEL <br />LEVEL <br />: 79.00 <br />80.00 in <br />INITIAL DIPPED WATER <br />LEVEL <br />: 0.00 <br />0.00 in <br />POST PUMPING WATER LEVEL <br />: 0.00 <br />0.00 in <br />-�dff,� RN -0 -'*0-- EE: E3 -T- FQ EEE $HEK.JK_-T­ <br />TEST INITIAL WATER LEVEL : 0.16 0.16 in <br />TEST FINAL WATER LEVEL : 0.16 0.16 in <br />WATER INGRESS : 0.00 in <br />BUBBLE SIGNATURES : No No <br />VACU-TECT TEST RESULT : Passed Passed <br />