Laserfiche WebLink
Vehicular Protection/Spacing <br /> • FG3301 <br /> o The tank is built to UL 2085 standard which provides inherent Vehicular/Ballistics <br /> protection. <br /> Recommended Next Inspection Schedule <br /> Tank# Product Tank Type Repairs to be made Next Inspection Date <br /> FG3301 I Diesel DW Horizontal J Yes 2/22/2036 <br /> Recommendations <br /> • FG3301 <br /> o The labels should be replaced soon. <br /> Requirements for Continued Service <br /> • FG3301 <br /> o Inspection and documentation of the cracks in the concrete slab under the tank need to <br /> be maintained and monitored for any change in width, length or severity. <br /> o "Safe Filling Level" labels need to be installed on all applicable portions of the tank. <br /> Professional Opinion <br /> The subject aboveground storage tank at Valley Pacific Petroleum, Valley Pacific Petroleum, <br /> 3550 S Hwy 99,Stockton, CA 95215 have been inspected using procedures found in STI SP-001 (5th <br /> Edition) publication "Standard for the Inspection of Aboveground Storage Tanks". <br /> It is the professional opinion of this firm that the tank is in acceptable condition, and fit for <br /> continued service (pending completion of the required repairs). <br /> This is not to be construed as an expressed or implied warranty of future performance. <br /> Should you have any questions or comments concerning this inspection report, please do not <br /> hesitate to contact the undersigned at 415-997-8034 or via email at miked@NWTLI.com. <br /> Michael Driggs <br /> miked@NWTLI.com <br /> SP-001 Inspector(R10125) <br /> 5 <br />