Laserfiche WebLink
will be changed to indicate that the Fire Chief <br /> or his appointed Deputy is the Incident <br /> Commander. Additional details including <br /> emergency contacts and phone numbers may be <br /> found at (enclosures J & K) of the report . <br /> (5) Item 32 - Failed to (1) train personnel on <br /> discharge prevention; (2) designate a person to <br /> be accountable for discharge prevention; of (3 ) <br /> schedule discharge prevention briefings at least <br /> annually. Corrective Action: The oil-handling <br /> personnel at DDJC that are required by 40 CFR <br /> 112 . 7 (F) to have training in the operation and <br /> maintenance of equipment and discharge <br /> prevention procedure protocols in order to <br /> prevent discharges are the fork lift operators <br /> (material handlers) and supervisors of Area C <br /> (POL drum storage area) and the HAZMAT employees . <br /> These personnel are trained to operate material <br /> handling equipment specifically to prevent <br /> discharges as well as First Responder training <br /> which outlines spill response protocols . The <br /> training records are kept in a database in the <br /> DDJC Training Office. The plan will be amended <br /> to indicate the correct location of the training <br /> records . Also note that the Hazardous Waste <br /> Program Manager is the designated person <br /> accountable for spill prevention and that the <br /> SPCC will be amended accordingly. <br /> (6) Item 53 - Failed to locate portable containers to <br /> prevent Discharge or provide sufficient <br /> secondary containment capacity that will hold <br /> the volume of the largest container plus <br /> sufficient free board to contain precipitation. <br /> Corrective Action: The two 55 gallon drums of <br /> lube oil at building 67 were immediately placed <br /> on a spill pallet (04/13/2010) . <br />