My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_PRE 2019
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
C
>
CHEROKEE
>
5463
>
2800 - Aboveground Petroleum Storage Program
>
PR0528482
>
COMPLIANCE INFO_PRE 2019
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
3/28/2019 3:47:41 PM
Creation date
10/18/2018 11:59:06 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2800 - Aboveground Petroleum Storage Program
File Section
COMPLIANCE INFO
FileName_PostFix
PRE 2019
RECORD_ID
PR0528482
PE
2832
FACILITY_ID
FA0009268
FACILITY_NAME
CHEROKEE FREIGHT LINES
STREET_NUMBER
5463
Direction
E
STREET_NAME
CHEROKEE
STREET_TYPE
RD
City
STOCKTON
Zip
95215-1120
APN
08712143
CURRENT_STATUS
01
SITE_LOCATION
5463 E CHEROKEE RD
P_LOCATION
99
P_DISTRICT
002
QC Status
Approved
Scanner
EJimenez
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
67
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
San Joaquin County AMENDED <br />Environmental Health Department <br />1868 East Hazelton Avenue, Stockton, California 95205-6232\ L <br />Telephone: (209) 468-3420 Fax: (209) 468-3433 Web: www.sjgov.orcl/ehd <br />Aboveground Petroleum Storage Act Inspection Report <br />Facility Name: <br />Facility Address: <br />Date: <br />CHEROKEE FREIGHT LINES <br />5463 E CHEROKEE RD, STOCKTON <br />January 13, 2017 <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />Item # <br />Remarks <br />715 <br />CFR 112.8(c)(8)(v) Failed to regularly test liquid level sensing devices to ensure proper operation. <br />Liquid level sensing devices on the motor oil and used oil tanks are not being tested regularly. Procedures and <br />frequency of testing for these devices were not addressed in the Spill Prevention, Control, and Countermeasure <br />(SPCC) plan. Liquid level sensing devices must be installed in accordance with CFR 112.8 and shall be regularly <br />tested to ensure proper operation. Immediately conduct all necessary testing of liquid level sensing devices, or <br />provide equivalence as allowed by CFR 112.7(x)(2). <br />This is a Class II violation. <br />718 <br />CFR 112.8(c)(11) Failed to provide sufficient secondary containment capacity for mobile or portable containers. <br />The 55 gallon waste diesel drum east of the truck shop and a 55 gallon drum of oily water next to the oil -water <br />separator skim tank were observed with no secondary containment. Portable oil storage containers must be <br />positioned or located to prevent a discharge and shall be furnished with a secondary means of containment sufficient <br />to contain the capacity of the largest single container with sufficient freeboard to contain precipitation. Immediately <br />provide sufficient secondary containment for this and all other portable containers at this facility, or provide <br />equivalence as allowed by CFR 112.7(a)(2). <br />This is a Class II violation. <br />724 <br />CFR 112.8(d)(4) Failed to regularly inspect aboveground valves, piping, and appurtenances. <br />Copies of recent inspection and testing records were not found on site. The most recent inspection forms were dated <br />March 2016. All aboveground valves, piping, and appurtenances shall be regularly inspected. Immediately inspect <br />aboveground valves, piping, and appurtenances and ensure inspections are done regularly, or provide equivalence <br />as allowed by CFR 112.7(a). <br />This is a Class II violation. <br />40 CFR 112.7 - SPCC Plan lacks full approval of management at a level of authority to commit the necessary <br />4010 <br />resources to implement the Plan. <br />The management approval section of the plan was signed by Gary Scannavino who is no longer with the business. <br />The Spill Prevention, Control, and Countermeasure (SPCC) Plan must have the full approval of management at a level <br />of authority to commit the necessary resources to fully implement the Plan. Immediately obtain required management <br />approval for the SPCC Plan for this facility. <br />This is a Class II violation. <br />Overall Inspection Comments: <br />An inspection checklist was provided to the facility operator on the day of inspection. The EHD has written the <br />complete report which replaces the initial checklist. <br />Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br />documenting the corrective actions that have been or will be taken for each violation, and any supporting <br />Page 8 of 9 <br />
The URL can be used to link to this page
Your browser does not support the video tag.