SWRCB, January 2002 <br />21. UNDER -DISPENSER CONTAINMENT (UDC) TESTING <br />Page of <br />Test Method Developed By: 11 UDC Manufacturer X Industry Standard L Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure 7 Vacuum X Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br />UDC#22-5&23-M UDC#23-5&24-M UDC#24-5&25-M UDC#25-5&26-M <br />UDC Manufacturer: Bravo Bravo Bravo Bravo <br />UDC Material: <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />UDC Depth: <br />30" <br />30" <br />30" <br />30" <br />Height from UDC Bottom to Top <br />12" <br />12" <br />12" <br />12" <br />of Highest Piping Penetration: <br />Height from UDC Bottom to <br />No Electrical <br />No Electrical <br />No Electrical <br />No Electrical <br />Lowest Electrical Penetration: <br />Penetrations <br />Penetrations <br />Penetrations <br />Penetrations <br />Condition of UDC prior to <br />Dry <br />Dry <br />Dry <br />Dry <br />testing: <br />Portion of UDC Tested <br />28" <br />28" <br />28" <br />28" <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />No <br />No <br />No <br />No <br />product and water)?* <br />Turbine shutdown response time <br />N/A <br />N/A <br />N/A <br />N/A <br />Is system programmed for fail- <br />No <br />No <br />No <br />No <br />safe shutdown?* <br />Was fail-safe verified to be <br />N/A <br />N/A <br />N/A <br />N/A <br />operational?* <br />Wait time between applying <br />5 Minutes <br />5 Minutes <br />5 Minutes <br />5 Minutes <br />water and starting test <br />Test Start Time: <br />8:25 <br />8:30 <br />8:35 <br />8:40 <br />Initial Reading (RI): <br />.001 <br />.001 <br />.001 <br />.001 <br />Test End Time. <br />8:55 <br />9:00 <br />9:05 <br />9:10 <br />Final Reading (RF): <br />.001 <br />.001 <br />.001 <br />.001 <br />Test Duration: <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />Change in Reading (RF-Ri): <br />0 <br />0 <br />0 <br />0 <br />Pass/Fail Threshold or Criteria: <br />.005/30 Minutes <br />.005/30 Minutes <br />.005/30 Minutes <br />.005/30 Minutes <br />Test Result: <br />Pass <br />Pass <br />Pass <br />Pass <br />Was sensor removed for testing? <br />Yes <br />Yes <br />Yes <br />Yes <br />Was sensor properly replaced and <br />Yes <br />Yes <br />Yes <br />Yes <br />verified functional after testing? <br />Comments — (include information on repairs made prior to testing, and recommended <br />M=Master <br />S=Satellite <br />ur`G9201b <br />nFE AP.ThAEN1 <br />22. UNDER -DISPENSER CONTAINMENT (UDC) TESTING <br />' If the entire depth of the UDC is not tested, specify how much was tested. If the answer to gny of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />