Laserfiche WebLink
SWRCB, January 2002 <br />24. FILL RISER CONTAINMENT SUMP TESTING <br />Page of <br />Facility is Not Equipped With Fill Riser Containment Sumps <br />Fill Riser Containment Sumps are Present, but were Not Tested <br />Test Method Developed By: ❑ Sump Manufacturer Industry Standard X Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: ❑ Pressure Vacuum X Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br />Sum Diameter: <br />Fill Sump # 5 -US <br />Fill Sump # Fill Sump # <br />Fill Sump # <br />42" <br />Sump Depth: <br />74" <br />Height from Tank Top to Top of <br />Highest Piping Penetration: <br />19 ''/z" <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />38" <br />Condition of sump prior to <br />testing: <br />Dry <br />Portion of Sump Tested <br />Water Line 43 ''/z" <br />Sump Material: <br />Fiberglass <br />Wait time between applying <br />water and starting test: <br />5 Minutes <br />Test Start Time: <br />10:15 <br />Initial Reading (Rj): <br />.001 <br />Test End Time: <br />10:45 <br />Final Reading (RF): <br />.001 <br />Test Duration: <br />30 Minutes <br />Change in Reading (RF -R,): <br />0 <br />Pass/Fail Threshold or Criteria: <br />.005/30 Minutes <br />Test Result: <br />Pass <br />Is there a sensor in the sump? <br />Yes <br />Does the sensor alarm when <br />either product or water is <br />detected? <br />Yes <br />Was sensor removed for testing? <br />Yes <br />Was sensor properly replaced and <br />verified functional after testing? <br />Yes <br />Comments — (include information on repairs made Prior to testinz and recommended <br />vi :Av ^ et t'r a <br />ENVIRONMEN1 AL , <br />DEPAH 1 ; <br />