SAN J o A Q u i N Environmental Health Department <br /> COUNTY— <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Name: Facility Address: Date: <br /> LIONUDAKIS FIREWOOD 20451 MCHENRY AVE. ESCALON July 27, 2018 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 714 CFR 112.8(c)(8)(i-iv) Failed to provide each container with a high level monitoring device. <br /> High level monitoring devices are not discussed in the SPCC plan. At least one of the following devices must be <br /> installed in each container: <br /> -High liquid level alarm with audible or visual signal <br /> -High liquid level pump cutoff device set to stop flow at a predetermined content level <br /> -Direct audible or code signal communication between the container gauger and the pumping station <br /> -Fast response system, such as digital computer, telepulse, or direct vision gauge. If a direct vision gauge is <br /> being used for determining the liquid level of each tank, a person must be present to monitor gauges and the overall <br /> filling of the tanks. <br /> Immediately install an approved liquid level sensing device in accordance with CFR 112.8 and implement necessary <br /> procedures to ensure that the devices are fully functional and in use at all times during tank filling operations, or <br /> provide equivalence as allowed by CFR 112.7(a)(2). <br /> This is a repeat violation, Class II. <br /> 715 CFR 112.8(c)(8)(v) Failed to regularly test liquid level sensing devices to ensure proper operation. <br /> Liquid level sensing devices have not been tested for any of the tanks. Procedures and frequency of testing for <br /> these devices were not addressed in the Spill Prevention, Control, and Countermeasure(SPCC)plan. Liquid level <br /> sensing devices must be installed in accordance with CFR 112.8 and shall be regularly tested to ensure proper <br /> operation. Immediately conduct all necessary testing of liquid level sensing devices, or provide equivalence as <br /> allowed by CFR 112.7(a)(2). <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by August 28, 2016. <br /> Please be aware as of January 1, 2013, all businesses are required to submit all new(or any changes to <br /> existing)Aboveground Petroleum Storage Act(APSA) information online to the California Environmental <br /> Reporting System (CERS) at http://cers.calepa.ca.gov in addition to any other relevant activities and required <br /> fields. No later than January 1, 2014, all APSA data must be entered and or updated in CERS. <br /> AFTER THE COMPLIANCE DATE,EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: ,July 27, 2018 Inspector: Inspector Phone: <br /> Printed Name and Title: CESAR RUVALCABA, REHS (209)953-6213 <br /> Amber Lionudakis, Parts Purchasing <br /> FA0010254 PR0523036 SCO01 07/2712018 <br /> EHD 28-01 Rev.11/07/2017 Page 8 of 8 Aboveground Petroleum Storage Act OR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />