Laserfiche WebLink
Inspection Summaty <br /> An STI SP001 formal external inspection that included visual examination and ultrasonic thickness testing was conducted. The <br /> inspection was completed on 2/12/2016. The tank is located at Interstate Oil,4900 E. Mariposa Road in Stockton, CA. The <br /> followinq is a detailed re ort of the inspection includinq findins and recommendations. <br /> 1.0 GenerallTank Information <br /> General Information Observations Comments/Recommendations <br /> Facility Name Interstate Oil -s <br /> Facility ID STOCKTON 1 <br /> Compliance Records Available? No <br /> anknolo y Work Order No. 6700693 <br /> Other <br /> • . :t .ns Comments/Recommendations <br /> Tank Nameplate _ None <br /> Tank Name/Number 1 iVl"t/Tt_.Iv i i <br /> Tank Layout(Horizontal,Vertical, other) Horizontal <br /> Tank Design (Single wall, double wall, other) Single Wall <br /> Tank Construction Material(carbon, Carbon <br /> stainless, other) <br /> Tank size (nominalgallons) 10000 <br /> Tank Shape Cylindrical <br /> Tank Length 27' <br /> Tank width/diameter/circumference 8' <br /> Tank Height N/A <br /> Tank Contents diesel <br /> Cathodic Protection None <br /> Continuous Release Detection Method Elevated <br /> CRDM <br /> Release Prevention Barrier(RPB) Concrete <br /> Spill Control Containment <br /> Foundations And Supports Observations Comments/Recommendations <br /> Other <br /> Tank Foundation Type Concrete pad <br /> Tank Foundation Condition Good/some small cracks <br /> Tank Support Type Steel saddles <br /> Tank Support Condition Good/some rust <br /> Tank Protection (bollards,fence, other) Concrete wall <br /> Other <br /> sbservations Comments/Recommendations <br /> Filling Procedures Posted At Fill As No Install signage at the fill point to document filling <br /> Required? procedures. ** <br /> "No Smoking"Signage Present As Required.Yes <br /> Emergency Contact Numbers Posted As No Emergency plan is required and should include posting <br /> Required? of emergency contact numbers. ** <br /> Tank Capacity And Tank ID Posted On The No Clearly label tank with capacity and ID.** <br /> Tank As Required? <br /> NFPA Signage-On The Tank,At Facility <br /> Entrance,And As Designated By Fire Code Yes <br /> Official. Labels Include Contents And NFPA <br /> 704 Diamond Hazard Signs. <br /> Other <br /> 3 <br />