Laserfiche WebLink
The following is an itemized list of aboveground petroleum storage act violations that <br /> have not been addressed for NORCAL TRANSPORT REFRIGERATION as of May <br /> 23, 2018. <br /> Open violations from February 02, 2016 inspection <br /> Violation#611 -Plan failed to include a description of potential equipment failure or provide equivalence. <br /> Potential equipment failure and the resulting spill for the used oil tank was not addressed in the Spill Prevention. <br /> Control, and Countermeasure(SPCC) Plan. The SPCC Plan must include a prediction of the direction, rate of flow, <br /> and total quantity of oil which could be discharged from the facility as a result of major equipment failure <br /> Immediately amend the SPCC Plan to include this information and submit a copy of the revision to the EH LLor JJ <br /> equivalence as allowed by 40 CFR 112.7(a)(2). No LASECA O�) tats'�L 5 I e Il.o <br /> Provide eq ence LO'S i <br /> 1-f av e b Dart S n G <br /> sh¢•1�� <br /> Violation #724 -Failed to conduct integrity and leak test on buried piping any time it is worked on. Ire V% <br /> No integrity testing was available for the buried diesel piping on site Buried piping shall be tested for integrity and <br /> leaks at the time of installation, modification. construction, relocation. or replacement. Immediately perform integrity <br /> and leak testing of this piping and ensure that piping is tested when required. or provide equivalence as allowed by <br /> CFR 112.7(a)(2). ThtS 1 5 C10N C s a� eve,sMO 1`1 V1-"5U CI <br /> 1 he1�- has <br /> eeti\ rV v <br /> 1 1 <br /> WS �p � 0 L-V <br /> 1itiOq'�lO� 5i�-+�'� i ►v5 1�a��� . a <br /> Page 1 of 1 <br />