Laserfiche WebLink
Hazardous Waste Tank System I [august <br /> Written Assessment per CCR Title 22 <br /> Applied Aerospace Structures, Inc., Stockton, CA 95206 2014 <br /> Volume calculation(s) <br /> The secondary containment volume is greater•than 80,000 gallons RECEIVE) <br /> The tank is indoors so the 25 year rain event does not apply. MAR 1 6 2015 <br /> The Neutralization tank is 670 gallons. <br /> The containment is sufficient. ENVIRONMENTAL <br /> HcAITu r)r=DODTAACtdT <br /> Visual inspection of containment area: <br /> The secondary containment is coated concrete which is Imperrreable. The <br /> containment is free of breaks, cracks or other defects. r <br /> The containment is rinsed of spills on a routine basis. 131L�Y <br /> The pocket sump contains hazardous waste and is not double walled. The <br /> pocket sump must have secondary containment <br /> Site Security: The neutralization system is indoors and with facility security. <br /> The area is routinely patrolled by the Stockton Police Department... <br /> Secondary Containment findings: The secondary containment system is of <br /> sufficient capacity and condition for the containment of releases from all tanks <br /> and ancillary equipment. Initials: <br /> Strandberg Associates 1(866) 388-0404 rwaterouyarwatercuy.com 15 <br />