Laserfiche WebLink
Appendix B <br /> Secondary Containment Calculations <br /> Stockton Pick-N-Pull <br /> rxtp�� <br /> Secondary Containment T <br /> h <br /> If �1 <br /> thft* � F <br /> Len 00 ft <br /> Northern Section 8.00 38.37 0 <br /> Southern Section 13.001 8.001 38.37 1035.00 DEC 082016 <br /> Gasoline Section 33.501 8.33 - 0.171 46.531 362 <br /> 'The dimensions on Drawing 15101000(Appendix C)were field verified;therefore manufacturer calculated volumes are uulized <br /> Tanks Length(ft)* Diameter ftVolume ft3' Volume(gal)* ENVIRONMENTAL HEALTH <br /> 01 6.17 3.25 44.12 330.00 DEPARTMJiENT <br /> 02 6.17 3.25 44.12 330.00 <br /> 03 6.17 3.25 44.12 330.00 <br /> 04 6.17 3.25 44.12 330.00 <br /> Al 4.17 3.25 29.41 220.00 <br /> A2 4.17 3.25 29.41 220.00 <br /> A3 4.17 3.25 29.41 220.00 <br /> A4 4.171 3.25 29.411 220.00 <br /> The dimensions on Drawings 3400220 and 3400330(Appendix C)were field verified;therefore manufacturer calculated <br /> volumes are utilized <br /> Tank Volume in Containment lower 28 Inches=79% <br /> Tanks Volume al Volume% Volume al <br /> 01 330.00 79% 260.70 <br /> 02 330.00 79% 260.70 <br /> 03 330.00 79% 260.70 <br /> 04 330.00 79% 260.70 <br /> Al 220.00 79% 173.80 <br /> A2 220.00 79% 173.80 <br /> A3 220.00 79% 173.80 <br /> 1A4220.00 79% 173.80 <br /> Note:GAS1/2 are double walled tanks on skids.Therefore,calculation of volume of displacement isn't required. <br /> Piping(longest single run <br /> Northern Section Length. ft Diameter ft Volume ft3 Volume al <br /> Stand to Header 11.00 0.131i0.13 1.01 <br /> Header to Tank 14.001 0.171 0.311 2.28 <br /> TOTALI 3.29 <br /> Piping(longest single run <br /> Southern Section I Len th ftDiameter ftVolume ft3 Volume al <br /> Stand to Header 11.001 0.131 1.01 <br /> Header to Tank 28.001 0.171 4.57 <br /> TOTALI 5.58 <br /> Piping(longest single run <br /> Gasoline Section I Length ft Diameter ftVolume ft3 Volume al <br /> Sum to Tanks outside 200.001 0.131 2451 18.36 <br /> TOTALI 18.36 <br /> Required Containment Volume <br /> Remaining <br /> 100% Tank Excess <br /> Largest Tank Ancillary Displacement Required Containment Capacity <br /> al Piping al al Volume al Volume al al <br /> -- <br /> Northern Section 330.00 3.29 608.30 941.59 1035.00 93.41 -� <br /> Southern Section 330.00 5.58 608.30 943.88 1035.00 91.12 <br /> Gasoline Section 0.00 18.36 0.00 18.36 361.99 343.63 <br /> created by:RS 7/11/16 <br /> reviewed by:JB 7/15/16 <br />