Laserfiche WebLink
Ch. 15,Art. 10-11 <br /> §66265.195.Inspections. <br /> (a)The owner or operator shall inspect,where present,at least once each operating day: <br /> (1)overfill/spill control equipment(e.g.,waste-feed cutoff systems, bypass systems, and drainage systems) <br /> to ensure that it is in good working order; <br /> (2)the aboveground portions of the tank system,if any,to detect corrosion or releases of waste; <br /> (3)data gathered from monitoring equipment and leak-detection equipment,(e.g., pressure and temperature <br /> gauges, monitoring wells)to ensure that the tank system is being operated according to its design; <br /> (4)the construction materials and the area immediately surrounding the externally accessible portion of the <br /> tank system including secondary containment structures(e.g.,dikes)to detect erosion or signs of releases of <br /> hazardous waste(e.g.,wet spots, dead vegetation);and <br /> (5)for uncovered tanks,the level of waste in the tank,to ensure compliance with section 66265.194(b)(3). <br /> (b)The owner or operator shall inspect cathodic protection systems, if present,according to,at a minimum, <br /> the following schedule to ensure that they are functioning properly: <br /> (1)the proper operation of the cathodic protection system shall be confirmed within six months after initial <br /> installation,and annually thereafter;and <br /> (2)all sources of impressed current shall be inspected and/or tested,as appropriate,at least bimonthly(i.e., <br /> every other month). <br /> (c)The owner or operator shall document in the operating record of the facility an inspection of those items <br /> in subsections(a)and(b)of this section. <br /> NOTE:Authority cited:Sections 208,25150 and 25159, Health and Safety Code. Reference: Sections 25159 and <br /> 25159.5, Health and Safety Code;40 CFR Section 265.195. <br /> HISTORY <br /> 1. New section filed 5-24-91;operative 7-1-91 (Register 91, No.22). <br /> §66265.196.Response to Leaks or Spills and Disposition of Leaking or Unfit-for-Use Tank Systems. <br /> A tank system or secondary containment system from which there has been a leak or spill,or which is unfit <br /> for use,shall be removed from service immediately, and the owner or operator shall satisfy the following <br /> requirements. <br /> (a)General emergency procedures.The owner or operator shall comply with applicable requirements of <br /> section 66265.56. <br /> (b)Cessation of use; prevention of flow or addition of wastes.The owner or operator shall immediately stop <br /> the flow of hazardous waste into the tank system or secondary containment system and inspect the system to <br /> determine the cause of the release. <br /> (c)Removal of waste from tank system or secondary containment system. <br /> (1) If the release was from the tank system,the owner or operator shall,within 24 hours after detection of <br /> the leak or, if the owner or operator demonstrates that that is not possible, at the earliest practicable time remove as <br /> much of the waste as is necessary to prevent further release of hazardous waste to the environment and to allow <br /> inspection and repair of the tank system to be performed. <br /> (2)If the release was to a secondary containment system,all released materials shall be removed within 24 <br /> hours or in as timely a manner as is possible to prevent harm to human health and the environment. <br /> (d)Containment of visible releases to the environment.The owner or operator shall immediately conduct a <br /> visual inspection of the release and, based upon that inspection: <br /> (1)prevent further migration of the leak or spill to soils or surface water;and <br /> (2)remove,and properly dispose of,any visible contamination of the soil or surface water. <br /> (e)Notifications,reports. <br /> (1)Any release to the environment,except as provided in subsection (e)(2)of this section,shall be reported <br /> to the Department within 24 hours of detection. <br /> (2)A leak or spill of hazardous waste is exempted from the requirements of subsection(e)of this section, <br /> but is not exempted from the requirements of section 66265.56, if it is: <br /> (A)less than or equal to a quantity of one(1)pound,and <br /> (B)immediately contained and cleaned-up. <br /> (3)Within 30 days of detection of a release to the environment,a report containing the following information <br /> shall be submitted to the Department: <br /> (A)likely route of migration of the release; <br /> (B)characteristics of the surrounding soil(soil composition,geology,hydrogeology,climate); <br /> (C)results of any monitoring or sampling conducted in connection with the release, (if available). If sampling <br /> or monitoring data relating to the release are not available within 30 days,these data shall be submitted to the <br /> Department as soon as they become available; <br /> (D)proximity to downgradient drinking water,surface water,and population areas;and <br /> (E)description of response actions taken or planned. <br /> (f)Provision of secondary containment, repair,or closure. <br /> (1) Unless the owner or operator satisfies the requirements of subsections(f)(2)thro ( 't .�ectlon <br /> the tank system shall be closed in accordance with section 66265.197. a ! E <br /> (2) If the cause of the release was a spill that has not damaged the integrity of the s to <br /> owner/operator may return the system to service as soon as the released waste is removed and repairs, if necessary, <br /> DEC 0 82016 <br /> Unofficial Title 22 m 2005 State of California,all rights reserved.May not be commercially reproduced or sold. 619/08 <br /> ENVIRONMENTAL HEALTH <br /> DEPARTP07-PST <br />