Laserfiche WebLink
ATTACHMENT C <br />Analvtical Results for Cooling Towers Blowdown Samples <br />Sampling Dates: 26 April, 22 May, 14 June, and 16 September, 1991 <br />Tower B-805 <br />Design Blowdown <br />Flow Rate (gpd) <br />1500 <br />Measured Blowdown <br />Flow Rate (gpd) <br />Measured Blowdown <br />Temperature ('F) <br />66 <br />pH (pH units) <br />8.83 <br />Flow Rate (gpd) <br />Average <br />332 <br />Maximum <br />720 <br />Temperature ('F) <br />Maximum <br />67 <br />Minimum <br />62 <br />pH (pH units) <br />Average <br />8.77 <br />Maximum <br />9.05 <br />TDS (mg/1) <br />Average <br />1800 <br />Maximum <br />2200 <br />Tower B-809 <br />Design Blowdown <br />Flow Rate (gpd) <br />1500 <br />Measured Blowdown <br />Flow Rate (gpd) <br />Measured Blowdown <br />Temperature ('F) <br />66 <br />pH (pH units) <br />8.83 <br />Flow Rate (gpd) <br />Average <br />220 <br />Maximum <br />360 <br />Temperature (° F) <br />Maximum <br />80 <br />Minimum <br />71 <br />pH (pH units) <br />Average <br />8.85 <br />Maximum <br />8.99 <br />TDS (mg/1) <br />Average <br />1933 <br />Maximum <br />3000 <br />Tower B-812 <br />Design Blowdown <br />Flow Rate (gpd) <br />1800 <br />Measured Blowdown <br />Flow Rate (gpd) <br />Measured Blowdown <br />Temperature ('F) <br />66 <br />pH (pH units) <br />8.83 <br />Flow Rate (gpd) <br />Average <br />198 <br />Maximum <br />225 <br />Temperature (°F) <br />Maximum <br />85 <br />Minimum <br />63 <br />pH (pH units) <br />Average <br />8.83 <br />Maximum <br />8.96 <br />TDS (mg/1) <br />Average <br />1600 <br />Maximum <br />1700 <br />Tower B-815' <br />Design Blowdown <br />Flow Rate (gpd) <br />1500 <br />Measured Blowdown <br />Flow Rate (gpd) <br />511 <br />Temperature ('F) <br />66 <br />pH (pH units) <br />8.83 <br />TDS (mg/1) <br />1600 <br />