JAN-17-2006 08:54 F—vice Station Systems 408 938 8888 P.08/12 <br /> SAMPLING PROTOCOL FOR ROUTINE PIPING/DISPENSER REMOVAUREPLACEMENT <br /> The following represents minimum sampling criterion required for closure compliance_ Soil samples collected shall be <br /> representative of native soils beneath the tank's invert (tank's bottom) at a collection depth not to exceed 2 - 4 feet. If <br /> contamination is documented during closure, an Unauthorized Release Notification must be completed and submitted within <br /> five(5)working days pursuant to California Health &Safety Code, Section 25295. <br /> DISPENSER SAMPLES <br /> AT LEAST ONE SAMPLE BELOW EACH DISPENSER <br /> PIPING AND STOCKPILE <br /> PIPING SOIL SAMPLES 1 Sample�every 20 Pineal feet <br /> DISPENSER &PIPING STOCKPILE SAMPLES 2 Samples every 50 cubic yards <br /> 4 <br />