My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO 2012-2013
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
C
>
COLONY
>
1553
>
2300 - Underground Storage Tank Program
>
PR0516526
>
COMPLIANCE INFO 2012-2013
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
5/28/2019 9:51:31 AM
Creation date
11/1/2018 10:44:13 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO 2012-2013
FileName_PostFix
2012-2013
RECORD_ID
PR0516526
PE
2361
FACILITY_ID
FA0012659
FACILITY_NAME
LOVE'S COUNTRY STORES OF CALIF #223
STREET_NUMBER
1553
STREET_NAME
COLONY
STREET_TYPE
RD
City
RIPON
Zip
95366
APN
24534024
CURRENT_STATUS
01
SITE_LOCATION
1553 COLONY RD
P_LOCATION
05
P_DISTRICT
005
QC Status
Approved
Scanner
LSauers
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
279
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
SAN JOAQUIN COUNTY <br />ENVIRONMENTAL HEALTH DEPARTMENT <br />1868 East Hazelton Avenue, Stockton, California 95205-6232 <br />Telephone: (209) 468-3420 Fax: (209) 468-3433 Web: www.slgov.org/ehd <br />UNDERGROUND STORAGE TANK (UST) PROGRAM INSPECTION REPORT CONTINUED <br />Facility Loves Country Store Adddress: 1553 Colony Drive, Ripon Datelity : <br />Name: Aug 13, 2013 <br />SUMMARY OF VIOLATIONS <br />CLASS I, CLASS II, or MINOR -Notice to Comply) <br />VIOLATIONS <br /># <br />C1 <br />C2 <br />M <br />Code Section <br />HSC = CA Health and Safety Code, CFR = Code of Federal Regulations <br />C1 = Class 1 violation; C2 = Class 2 violation, M = Minor violation <br />311. The diesel (Tank 1) line leak detector failed to detect a leak when tested. All line leak detectors <br />shall be capable of detecting a 3 -gallon per hour leak at 10 psi. Immediately have a properly licensed, <br />Non -Pressurized Piping (continued) <br />702 <br />immediately, there is a possibility that the diesel UST system may be red tagged to prevent fuel inputs. <br />Minor -Notice to Comply: <br />204. The designated operator failed to check and note the correct test dates for the monitoring system <br />CCR 2643(e) <br />Biennial tightness test of gravity piping not performed (pre -January 1, 1984) (M1) <br />703 <br />they were done. Ensure that designated operators performing monthly inspections at this facility are <br />including all of the required information on the reports. <br />Complete and submit a copy of the Return to Compliance Certification form with a statement of how <br />CCR 2643(d) <br />Triennial line test for conventional suction piping not performed (pre -January 1, 1984) (M1) <br />leak. <br />ALL EHD STAFF TIME ASSOCIATED WITH FAILING TO COMPLY BY THE ABOVE NOTED DATES WILL BE BILLED AT THE CURRENT HOURLY RATE. <br />Other Violations <br />999 <br />Other: <br />See attached "Continuation — Official Inspection Report" for violation(s) not listed above. <br />SUMMARY OF VIOLATIONS <br />CLASS I, CLASS II, or MINOR -Notice to Comply) <br />Onsite to observe monitoring system certification and conduct routine UST inspection: <br />Class II Violations: (306 and 311): <br />306. A fuel leak was found at the dispensers 17/18 and 22/23. All primary containment must be product <br />tight. The leak at the dispenser 22/23 was corrected at the time of inspection. Immediately discontinue <br />use of failed piping at the dispenser 17/18 (damaged by a vehicle collision on S -.2-20a), and have <br />a properly licensed, trained, and certified contractor replace or repair the failed piping. Obtain a permit <br />from the EHD if a major repair/modification is necessary. If the failed component can't be replaced <br />immediately, there is a possibility that the diesel UST system may be red tagged to prevent fuel inputs. <br />311. The diesel (Tank 1) line leak detector failed to detect a leak when tested. All line leak detectors <br />shall be capable of detecting a 3 -gallon per hour leak at 10 psi. Immediately have a properly licensed, <br />trained, and certified contractor repair or replace the failed leak detector (LG 113-x listed, if applicable) <br />and obtain a permit within one business day from the EHD. If the failed leak detector can't be replaced <br />immediately, there is a possibility that the diesel UST system may be red tagged to prevent fuel inputs. <br />Minor -Notice to Comply: <br />204. The designated operator failed to check and note the correct test dates for the monitoring system <br />certification and secondary containment testing on the 01-07-2013 and 07-26-2013 designated operator <br />monthly inspection reports. During the monthly inspection, the designated operator shall check that all <br />required testing and maintenance for the UST system have been completed and document the dates <br />they were done. Ensure that designated operators performing monthly inspections at this facility are <br />including all of the required information on the reports. <br />Complete and submit a copy of the Return to Compliance Certification form with a statement of how <br />each violation was corrected, including supporting documentation, by September 13, 2013. Note: <br />provided a copy of the Recording Requirements for Unauthorized Releases form for the existing fuel <br />leak. <br />ALL EHD STAFF TIME ASSOCIATED WITH FAILING TO COMPLY BY THE ABOVE NOTED DATES WILL BE BILLED AT THE CURRENT HOURLY RATE. <br />THIS FACILITY IS SUBJECT TO REINSPECTION A ANY TME AT EHD'S CURRENT HOURLY RATE. <br />Inspector <br />�ijBy: <br />Title <br />EHD 23-02 Rev 04/19/12 age US ECTION REPORT <br />
The URL can be used to link to this page
Your browser does not support the video tag.