Laserfiche WebLink
Seismic/Anchoring findings: The tank as designed and op ted, and the <br /> containment area in which it is located are adequately anchl and are <br /> seismically sound. Initials: <br /> Leak Test: Tank has been in service for nine years. Visual inspection did not <br /> show any evidence of tank leakage, weld cracks or significant corrosion. LIT <br /> analysis shows the tank to be in as built condition. <br /> ' Figure 6, Picture of the Waste Anti-freeze Tank Interstice <br /> Tracy Chrysler Jeep Waste-Antifreeze Tank Thickness Readings <br /> Top Side <br /> Reading into in mm In <br /> 1 3 0.12 28 0.11 <br /> 2 3 0.12 2.9 <br /> ' 3 3 0.12 2.8 0.11 <br /> 4 3 0.12 28 0.11 <br /> 5 3 0.12 2.8 0.11 <br /> 6 3 0.12 2.8 0.11 <br /> 7 3 012 2.8 0.71 <br /> 8 3 0.12 28 0.11 <br /> 9 3 0.12 28 0.11 <br /> 10 3 0.12 28 0.11 <br /> average 3 0.11811 2.82 0.111024 <br /> standard deviation 0 0 0.042164 O.00166 <br /> Figure 7, UTG readings on tank shell and piping. Small Standard Deviation indicates little <br /> or no internal corrosion. <br /> ' Tracy Chrysler Jeep 7 Waste Anti-freeze Tank <br />