Laserfiche WebLink
AqWd (' SERVICE ORDER <br /> Service Company <br /> CUSTOMER Tracy Chrysler / Hyundai DATE 18 Aug2009 <br /> 3460 Naglee Rd. _ TIME <br /> Tracy, CA 95304 BY Larry <br /> CONTACT Ron Imperiale P.O. # <br /> PHONE 209-520-1800 NEXT SERVICE <br /> SERVICE ORDER: <br /> ChEysler dealership: Tested High Level Alarm and Secondary Containment <br /> Alarm for Waste Oil and Waste Antifreeze tanks. Extended Waste Oil secondary <br /> level sensor to about 2" from bottom of tank (was set at about 3 feet from <br /> ' <br /> bottom). Replaced blown fuse in Waste Oil alarm panel New bulb needed for <br /> SecondaryContai=ent Alarm light on the Waste Oil alarm panel Tested all <br /> ' four sensors/alarms to be functional. Applied temporary identification tape for <br /> the alarm lights to indicate "high" and "secondary" alarms. Permanent labels _ <br /> need to be applied. <br /> ' <br /> Hyundai dealership: Tested High Lever Alarm for the Waste Oil and Waste <br /> Antifreeze tanks. Both alarms tested good. Furnished and installed Simpson <br /> HL33A seismic restraint clips, 10 total to restrain the Waste Oil and Waste <br /> Antifreeze tanks. Clips anchored using 1/2" diameter concrete wedge anchor <br /> bolts with 3" embedment depth. <br /> COMMENTS <br /> CUSTOMER SIGNATURE DATE <br /> Aquadynamics Service Co. <br /> ' 1221 Park Ave., Ste. A,San Jose, CA 95126 Cell (408) 591-6127 <br /> 1 Tracy Chrysler Jeep 20 Waste Anti-freeze Tank <br />