0 <br /> Pg.4 of 4 <br /> INITIAL DISCREPANCIES and RECOMMENDED CORRECTIONS <br /> 1. Waste Oil level Indication Gauge required, may combine with overfill Alarm per Title 22. <br /> i.e. battery operated audio overfill gauge. i.e. 1 @ Krueger KSALARM <br /> 2. Maintain Daily Inspection record or. site. (22 CCR§66265.195) <br /> 3. New installations may Require Emergency Relief Venting on Primary 1,000 GA AST <br /> where tank is exposed to heating. i.e. 1 @ Morrison fig 244 6"threaded IPS 16 oz. <br /> There is no 6"threaded opening available to update.The likelihood of sustained pool fire <br /> exposure requiring emergency venting with single AST in pan is minimal when <br /> combined with frequent documented inspections of pan volume.To assure partial <br /> emergency venting, install Morrison fig 244 4"threaded 16 oz. ERV where current <br /> normal vent is located and relocate existing normal vent to available threaded outlet. <br /> 4. Security fencing if required by regulatory authority,may include enclosure of waste <br /> coolant and used filter drums. Suggest plastic pallet pans for secondary containment, <br /> DOT hazardous material drums and tarp cover. <br /> 5. A clearance between pan bottom and concrete (PCC)floor is necessary to readily <br /> identify any release to the PCC floor. Suggest removal of waste oil tank after emptying, <br /> installing 3 each channel steel skids across bottom of pan,welded at outside edge of <br /> pan. Install minimal steel cradle inside pan to prevent AST from shifting. <br /> 6. Clean floor in area of pan to ease detection of leakage or spillage. <br /> RECEIVED <br /> MAR 13 2015 <br /> ENVIRONMENTAL <br /> HrA'Tu ncoe0T4AChM <br />