Laserfiche WebLink
10.5.1 All primary tanks 2000 gallons or larger shall be measured for tank wall thickness at <br />6", 1ft., 2ft. and 3ft. on the tank sidewall height at 0° and 1800 around the tank circumference <br />with 00 being the tank manway and going counter -clockwise per ANSI standard drafting <br />specifications. A copy of this test report can be ordered when placing the original tank <br />order. All tanks shall meet design thickness requirements and tolerances. <br />10.5.2 Tanks smaller than 2000 gallons are only periodically measured at the start of a <br />production run or after any design changes. Customers can place an order for tank wall <br />thickness measurements on smaller tank sizes when placing the original order. A copy of <br />the test report will be provided if ordered. <br />10.6 Hydrostatic Water Test <br />10.6.1 The hydrostatic water test shall consist of filling the primary tank to brim full capacity <br />for a minimum of four hours and conducting a visual inspection for leaks. A hydrostatic water <br />test will be conducted if ordered by the customer. <br />10.7 Workmanship <br />10.7.1 The finished tank wall shall be free, as commercially practicable, of visual defects <br />such as foreign inclusions, air bubbles, pinholes, pimples, crazing, cracking and <br />delaminations that will impair the serviceability of the vessel. Fine bubbles are acceptable <br />with Type II tanks to the degree in which they do not interfere with proper fusion of the resin <br />melt. <br />10.7.2 All cut edges where openings are cut into the tanks shall be trimmed smooth. <br />Table III — Fitting and Accessory Schedule <br />Tank Number TNK - TNK - TNK - TNK - <br />Description Quantity /Size Quantity / Size Quantity I Size Quantity / Size <br />Inlet nozzle <br />Top draw outlet nozzle <br />Drain (transition fitting) <br />Overflow <br />Vent <br />Surge Protection Lid <br />Fill <br />External fill pipe <br />Internal fill pipe <br />Manwa <br />Threaded / vented <br />Threaded <br />Hinged <br />Bolted / Sealed <br />Ladder / FRP <br />Galvanized Steel <br />Lifting Lugs <br />Tie -down Lugs <br />Seismic/Wind Tie -down <br />Galvanized Steel <br />304 SS <br />28 2014 <br />4ENTAL HEALTH <br />ARTMENT <br />