Laserfiche WebLink
gRAIG&SIAMILTON MEAT CO. <br /> 721 N. UNION <br /> STOCKTON CA. <br /> TANK TESTER VER 2.01 <br /> FUEL TYPE: DIESEL <br /> CAPACITY TANK 1: 10032 GALLONS <br /> TEMPERATURE COEFFICIENT: 455 ppm/deg F <br /> TEST CRITERIA: +0.050 GPH TO -0.050 GPH <br /> 02/26/89 TEST TIME FROM 11: 14 TO 11:47 <br /> DATA ANALYSIS INDICATES: <br /> A GROSS VOLUME CHANGE OF: -0.020 GALLONS <br /> A VOLUME CHANGE DUE TO TEMPERATURE OF: -0.013 GALLONS <br /> A LIQUID VOLUME RATE OF CHANGE OF: -0.017 GPH <br /> WITH A 99 % CONFIDENCE INTERVAL OF: +/-0.001 GPH <br /> (-0.016 TO --0.018 GPH) <br /> TESTER�,✓����� . . . .i '�-L� <br /> CUSTOMER. . . . . . . . . . . . . . <br />