Laserfiche WebLink
ITTSIntegrity Tank Testing Systems, Inc. <br /> January 28, 1992 <br /> r <br /> Mr. Tony Valenzuela <br /> Roto-Rooter Sewer Service <br /> 3480 East Carpenter Road <br /> Stockton, California 95205 <br /> Dear Mr. Valenzuela: <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank. <br /> Enclosed are copies of the test worksheet:., graphs, and/or <br /> computer summation for your submittal to the appropriate <br /> governmental agency. Individual computer generated readings <br /> will be forwarded as r9quested. <br /> A tank system may be considered tight, according to the <br /> current regulations if the the test results shown below do <br /> not exceed 0.05 gph. If the results are beyond this <br /> parameter, an unauthorized release may have occurred, and <br /> you should consider taking remedial action. <br /> TANK # OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> Northwest 1, 000 Diesel - .008 Yes <br /> Southeast 10, 000 U/L Gas - .028 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> nye <br /> W. N. Savage <br /> Certified Tester <br /> 800 262-8378 166 Fronk West Circle Stockton, CA 95206 (209) 466-8036 <br />