INVOICE #WC000304 USTest 2000 / P TEST DATE: 10/30/95 <br /> CHAMPION PRECISION TANK TESTING <br /> P.O. BOX 13059 <br /> SACRAMENTO, CALIF, 95813-3059 <br /> TANK STATUS EVALUATION REPORT <br /> ----------------------------- <br /> ***** CUSTOMER DATA ***** ***** SITE DATA ***** <br /> ROTO-ROOTER ROTO-ROOTER <br /> 14985 WASHINGTON 3480 EAST CARPENTER RD. <br /> CARPENTER AND HWY 99 FRONTAGE <br /> SAN LEANDRO,CA. STOCKTON,CA. <br /> 94578 <br /> CONTACT: RON CONTACT: SHOP <br /> PHONE #: 510-483-2324 PHONE #: <br /> ***** COMMENT LINES ***** <br /> CURRENT EPA STANDARDS DICTATE <br /> THAT FOR UNDERGROUND FUEL TANKS, THE MAXIMUM ALLOWABLE LEAK/GAIN RATE <br /> OVER THE PERIOD OF ONE HOUR IS .05 GALLONS. <br /> TANK #1: DIESEL FUEL 2 TYPE: STEEL RATE: .005419 G.P.H. LOSS <br /> TANK IS TIGHT. <br /> TANK #2: REG UNLEADED TYPE: STEEL RATE: .006870 G.P.H. GAIN <br /> TANK IS TIGHT. <br /> OPERATOR: <br /> SIGNATURE: 13 DATE: 1 d_30-cos <br /> , \� 1 Q2.13a-`�-- <br /> lll "u- ----- - <br />