Laserfiche WebLink
INTEGRITY TANK TESTING SERVICES <br /> P. 0. BOX 691736, STOCKTON, CA. 95269 <br /> MAR 29W3 <br /> January 28,1993 FNVIRONMEPJTAL HEALTH <br /> PIMI1`/ Vii t <br /> ROTO ROOTER SEWER SERVICE <br /> 3480 CARPENTER ROAD <br /> STOCKTON, CA, 95205 <br /> Dear Mr. Brown <br /> Following is a summary of the precision t Sft we recently conducted on your <br /> underground storage tank at the dbove site. <br /> Enclosed are copies of the test worksheet, graphs, andfor computer generated <br /> summations for your submittal to the appraprtes governmental agency. <br /> A tank system may be considered tight, according to the current regulations if the test <br /> results shown below do not exceed 0.05 gph. if the results are beyond this parameter, <br /> an unauthorized release may have occurred, and you should consider taking remedial <br /> action. <br /> TANK#OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS PARAMETERS <br /> NIW Tank 1,000 Diesel Fuel +.000 Yes <br /> S/ET 10,440 Gasoline -.011 Yes <br /> Please advise if you need additional information or service <br /> v Sincerel , <br /> W. N. Savage; <br /> Certified Tester = <br /> "Ift <br /> a N$!tj 2094T44375 EREI: ($� gs1'=I is <br /> � •m <br /> i <br />