Laserfiche WebLink
STOCKTON UN. SCH. DIST. <br /> EDISON HIGH SCHOOL <br /> STOCKTON CA. <br /> TANK TESTER VER 2.01 <br /> FUEL TYPE: REGULAR <br /> CAPACITY TANK 1 : 506 GALLONS <br /> TEMPERATURE COEFFICIENT: 675 ppm/des F <br /> TEST CRITERIA: +0.050 GPH TO -0.050 GPM <br /> 03/28/90 TEST TIME FROM 09:40 TO 10: 13 <br /> DATA ANALYSIS INDICATES: <br /> A GROSS VOLUME CHANGE OF: -0.014 GALLONS <br /> A VOLUME CHANGE DUE TO TEMPERATURE OF: -0.005 GALLONS <br /> A LIQUID VOLUME RATE OF CHANGE OF: -0.017 GPH <br /> WITH A 99 R CONFIDENCE INTERVAL OF: +/-0.001 GPH <br /> (-0.017 TO -0.018 GPH) <br /> TESTERS <br /> CUSTOMER. . . . . . . . . . . . . . <br />