Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for VANCO TRUCK-AUTO PLAZA as of November 28, 2017. <br /> Open violations from June 22, 2017 inspection <br /> Violation#101 -No permit to operate. <br /> A permit to operate the UST system has not been issued due to the outstanding historical violations, specifically <br /> violations in connection with the secondary containment testing. No person may own or operate an UST unless a <br /> permit for its operation has been issued by the local agency to the owner or operator of the UST system. <br /> Immediately obtain a permit to operate a UST system from the EHD. An "Operating without a Permit" penalty <br /> applies. <br /> Violation 9307 -Monitoring system of the interstitial space of a double walled system not maintained. <br /> The racing fuel annular sensor failed to activate an audible and visual alarm when tested and, therefore, the tank is <br /> not monitored. The interstitial space shall be monitored with a monitoring system connected to an audible and <br /> visual alarm system. Immediately contact a properly licensed, trained, and certified contractor to replace the failed <br /> component with a functional component(LG 113-x listed, if applicable) under permit and inspection procedures of <br /> the EHD within one business day. <br /> Page 1 of 1 <br />