Laserfiche WebLink
b. `i <br /> STOCKTON SERVICE STATION EQUIPMENT CO2999AR _2 AH 11: 44 <br /> 808 N. UNION STREET <br /> STOCKTON, CA 95205-4152ENviRONMENrAL <br /> UNTY <br /> PHONE 209.464.8333 FAX 209.464.8349 HEALTH DEPARTMENT <br /> LDT-890 LEAK DETECTOR TEST RECORD <br /> CUSTOMER: Rancho San Miguel DATE: February 28,2006 <br /> LOCATION: 610 Cherokee Lane <br /> CITY: Lodi STATE: CA ZIP: 95240 <br /> TECHNICIAN: Eric Molgaard <br /> -- Submersible Pump Identification <br /> Manufacturer Model Serial Number <br /> Fe Petro STPV52-VLZ-28 04041907 <br /> Leak Detector Identification <br /> Manufacturer Description Other Style Leak Detector <br /> Fe Petro ReHular Unlead <br /> Diaphragm-type <br /> Piston-type X <br /> Leak Detector in Submersible Pump <br /> Test at Dispenser <br /> 1. Operating Pump Pressure 30 psi (Purging Test System) <br /> 2. Gallons per hour rate 3.0 (Leak Test,Phase 1) <br /> 3. Line pressure with pump shut off 15 psi (Leak Test Phase 1) <br /> 4. Bleed-Back Test with pump off 250 ml (gleed-back Test) <br /> 5. Step through time to full flow 5 seconds (Step-through Time) <br /> 6. Leak detector stays in leak search position. (Leak Test Phase I1)Yes X No <br /> LEAK DETECTOR TEST <br /> Note: Pass=Leak detector fits test protocol <br /> Fall =Leak detector fails test protocol <br /> Pass X <br /> Fail <br /> Form 8900 <br />